Alarm
ID
Alarm
Name
Alarm
Severity
Possible Causes Troubleshooting
2064 Device
fault
Major Cause ID = 1–5, 7–
12
An unrecoverable
fault occurs on a
circuit inside the
inverter.
Turn o the AC output switch and DC
input switch, and then turn them on
after 5 minutes. If the alarm persists,
contact your dealer or Huawei technical
support.
NOTICE
Cause ID = 1: Perform the preceding
operations when the PV string current is less
than 1 A.
2065 Upgrade
failed or
version
mismatch
Minor Cause ID = 1–4, 7
The upgrade is not
completed
normally.
1. Perform an upgrade again.
2. If the upgrade fails several times,
contact your dealer or Huawei
technical support.
61440 Faulty
monitorin
g unit
Minor Cause ID = 1
● The ash
memory is
insucient.
● The ash
memory has bad
sectors.
Turn o the AC output switch and DC
input switch, and then turn them on
after 5 minutes. If the alarm persists,
replace the monitoring board or contact
your dealer or Huawei technical support.
2067 Faulty
power
collector
Major Cause ID = 1
The power meter is
disconnected.
1. Check whether the congured power
meter model is the same as the
actual model.
2. Check whether the communications
parameters of the power meter are
the same as the RS485
congurations
of the inverter.
3. Check whether the power meter is
powered on and whether the RS485
communications cable is connected.
SUN2000-(12KTL-25KTL)-M5 Series
User Manual 8 Maintenance
Issue 03 (2023-02-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 73