● 220: The output voltage is 220 V AC.
● 230: The output voltage is 230 V AC (default).
● 240: The output voltage is 240 V AC.
Step 6 Operate the UPSs one by one and set the number of UPSs connected in parallel to
2 or other values based on site requirements.
● Default value: 1
● Value range: 1–4
Step 7 Set the battery capacity to 100 Ah (or other values based on site requirements)
and press ON/MUTE+SELECT to return to the standby screen.
● Default value: 100 Ah
● Value range: 50–2400 Ah. The value is incremented by 50 Ah each time you press
SELECT.
● Battery string sharing enabled: When setting the battery capacity, set the total battery
string capacity for each UPS.
● Battery string sharing disabled: When setting the battery capacity, set the capacity of
the battery string connected to each UPS.
Step 8 Press and hold ON/MUTE on each UPS in the parallel system for more than 5s.
The UPS parallel system transfers to normal mode.