Figure 3-3 UPS mounting ear dimensions (unit: mm)
3.4 Preparing Power Cables
NO TICE
You are advised to install a disconnector for the UPS input.
A 2-pole disconnector must be used if the UPS is used to power IT systems.
The UPS can generate large leakage currents. A residual current device (RCD) is
not recommended. If leakage protection is required, select a recommended
circuit breaker.
The leakage current of the 6 kVA UPS is less than 100 mA.
When selecting an earth leakage circuit breaker, consider the leakage current of
the UPS and downstream loads.
Battery cables should not be longer than 10 m.
For the 6 kVA model, use PE cables that have a cross-sectional area of 6 mm
2
and 6 mm
2
M4 OT terminals.
The UPS battery input terminal has a voltage of 56 V 10 seconds before
batteries are connected.
UPS2000-G-6KRTLL
User Manual 3 Installation
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 26