● 220: The output voltage is 220 V AC.
● 230: The output voltage is 230 V AC (default).
● 240: The output voltage is 240 V AC.
Step 5 Set the battery capacity to 100 Ah (or other values based on site requirements)
and press ON/MUTE+SELECT to return to the standby screen.
● Default value: 100 Ah
● Value range: 50–2400 Ah. The value is incremented by 50 Ah each time you press
SELECT.
● When setting the battery capacity, set the capacity of the battery string connected to
the UPS.
Step 6 Press and hold ON/MUTE for more than 5s. Release the button when you hear a
beep sound. The UPS starts to work in normal mode.
Figure 5-4 Normal mode
Step 7 After you ensure that the UPS runs properly, switch on the AC output circuit
breaker Q for the UPS to start the load.
----End
5.2.1.2 Cold-Starting the UPS Using Batteries
Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Press ON/MUTE to start the UPS. The UPS will enter standby mode.
UPS2000-G-6KRTLL
User Manual 5 Operations
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 96