NO TE
220: The output voltage is 220 V AC.
230: The output voltage is 230 V AC (default).
240: The output voltage is 240 V AC.
Step 5 Set the battery capacity to 100 Ah (or other values based on site requirements)
and press ON/MUTE+SELECT to return to the standby screen.
NO TE
Default value: 100 Ah
Value range: 50–2400 Ah. The value is incremented by 50 Ah each time you press
SELECT.
When setting the battery capacity, set the capacity of the battery string connected to
the UPS.
Step 6 Press and hold ON/MUTE for more than 5s. Release the button when you hear a
beep sound. The UPS starts to work in normal mode.
Figure 5-4 Normal mode
Step 7 After you ensure that the UPS runs properly, switch on the AC output circuit
breaker Q for the UPS to start the load.
----End
5.2.1.2 Cold-Starting the UPS Using Batteries
Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Press ON/MUTE to start the UPS. The UPS will enter standby mode.
UPS2000-G-6KRTLL
User Manual 5 Operations
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 96