Huawei UPS2000-G-6KRTLL - Installing Battery Cables

Huawei UPS2000-G-6KRTLL
125 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NO TE
K
m
indicates the general AC input circuit breaker, K
m
1 indicates the UPS 1 input circuit
breaker, K
m
2 indicates the UPS 2 input circuit breaker, Q indicates the general AC output
circuit breaker, Q1 indicates the UPS 1 output circuit breaker, Q2 indicates the UPS 2 output
circuit breaker, K
b
indicates the general battery circuit breaker, K
b
1 indicates the UPS 1
battery circuit breaker, and K
b
2 indicates the UPS 2 battery circuit breaker.
----End
3.6.2 Installing Battery Cables
Procedure
Step 1 Switch
o the upstream AC circuit breakers for the UPSs.
Step 2 Remove the battery terminal covers.
Step 3 Connect a cable between the PE terminal and the cabinet ground bar.
Figure 3-13 Installing the battery PE cable
(1) Ground bar
Step 4 Install positive and negative battery cables.
UPS2000-G-6KRTLL
User Manual 3 Installation
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 33