No. Item Expected Result
2 Cable connection All cables are connected securely and
correctly, and they are free of damage.
Bolts are tightened to specied torque
using a torque wrench.
3 Cable connection to USB,
network, and other ports
Signal cables to USB, network, and
other ports are connected securely and
correctly.
4 Cable labels Labels are neatly attached to both
ends of each cable, and the
information on the labels is concise
and legible.
5 Ground cable connection The UPS ground cable is securely
connected to the equipment room
ground bar. Use a multimeter to
measure the resistance between the
UPS ground cable and the equipment
room ground bar. The resistance is less
than 0.1 ohm.
6 Spacing between cable ties Distances between cable ties are the
same, and no burr exists.
7 Operating environment The inside and outside of the cabinet
are free from conductive dust or other
sundries.
UPS2000-G-6KRTLL
User Manual 3 Installation
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 37