Name Display Description
Password setting Initial password:
000001
You are advised to
change the initial
password after
installation.
On the password
login screen, press
and hold ON/MUTE,
SELECT, and OFF/
ENTER at the same
time for 3s to restore
the initial password.
Changing the
password: Press ON/
MUTE or SELECT to
set the
rst digit of
the password, press
OFF/ENTER to
conrm the setting,
set the remaining
digits of the
password in
sequence in the
same way, and press
OFF/ENTER. The
password is changed
successfully.
Altitude-based
derating
Default value: 1000
m. When the altitude
exceeds 1000 m, the
output power is
derated by 1% for
each additional 100
m. The power can be
derated down to
70%.
Value range: 1000–
4000 m
Battery capacity
test
Battery capacity test
disabled (default)