Alarm ID Alarm
Name
Severity Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
03 High
battery
voltage
Critical The alarm
is
automatical
ly cleared
when the
battery
voltage is
lower than
58 V.
The battery
voltage is
greater
than 60 V
for 3s.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
Possible
cause:
The
battery
is faulty.
Measure:
Replace the
battery or
discharge
the battery
to a normal
voltage.
Possible
cause:
The
sampling
is faulty
due to
environ
mental
factors.
Measure:
Send the
device to
the
maintenanc
e center.
UPS2000-G-6KRTLL
User Manual 4 Control Panel
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 65