User Manual
HV Diagnostics Page 40 Rev 9.0
Step Procedure (Reporting) Example
R 1:
DUT
Specify the type of DUT. Select one of the
following options:
Cable
• Motor
• Generator
• Transformer
Switchgear
• Other
• Vacuum Bottle
R 2:
Voltage Rating
Specify the voltage rating of the DUT.
This is the nameplate rating of the DUT and
does NOT refer to the test voltage!
Rotate navigation knob (5) to increase or decrease
voltage rating value:
• Min rating. = 0.1 kV; Max rating= 50.0 kV
R 3:
Insulation
(only applicable
for Cables)
Specify one of the following cable insulation types:
XLPE
• PILC
• EPR
• PE
PVC
• HYBRID
(combination of types)
• OTH. (other)
R 4:
Report Title
Set report name
• User defined entry, typically the cable number
or ID for cable testing
R 5:
Phase
(Extended only)
Specify circuit phase
• User can define up to 3 phases if required
R 6:
Company
(Extended only)
Specify company name
R 7:
Region
(Extended only)
Specify region name
What is the
Device Under Test?
Cable
What is the
Voltage Rating of DUT?
1.0kV
DUT: Cable
Insulation?
XLPE
DUT: 1.0kV Cable
Start New / Report Details
Circuit / Line ID
circuitALPHA
DUT: 1.0kV Cable XLPE
Start New / Report Details
phaseRED
DUT: 1.0kV Cable XLPE
Start New / Report Details
company HV
DUT: 1.0kV Cable XLPE
Start New / Report Details
region CHEROKEE
DUT: 1.0kV Cable XLPE