6 APPENDIX
27
6.10. Appendix 10
Cable specification
1. Single phase unit
MCA
Phase line
AWG
Earth line
Signal line
No more
than 13A
2
1.3mm
2
16
1.3mm
2
n
0.5mm
2
13~18A
2
2.1mm
2
14
2.1mm
2
18~25A
2
3.3mm
2
12
3.3mm
2
25~30A
2
5.3mm
2
10
5.3mm
2
30~40A
2
8.4mm
2
8
8.4mm
2
40~55A
2
13 3mm
2
6
13.3mm
2
55~70A
2
21.2mm
2
4
21.2mm
2
MOP
MCB
Creepage protector
No more
than 13A
20A
30mA less than 0.1 sec
13~25A
40A
30mA less than 0.1 sec
25~30A
40A
30mA less than 0.1 sec
30~40A
63A
30mA less than 0.1 sec
40~55A
80A
30mA less than 0.1 sec
55~70A
100A
30mA less than 0.1 sec
2. Three phase unit
Nameplate
maximum
current
Phase line
AWG
Neutral line
Earth line
Signal line
No more
than 13A
3
1.3mm
2
16
1.3mm
2
1.3mm
2
n
0.5mm
2
13~18A
3
2.1mm
2
14
3.3mm
2
2.1mm
2
18~25A
3
3.3mm
2
12
3.3mm
2
3.3mm
2
25~30A
3
5.3mm
2
10
3.3mm
2
5.3mm
2
30~40A
3
8.4mm
2
8
3.3mm
2
8.4mm
2
40~55A
3
13.3mm
2
6
3.3mm
2
13.3mm
2
55~70A
3
21.2mm
2
4
3.3mm
2
21.2mm
2
When the unit will be installed at outdoor, please use the cable which can against UV.