4.0 Error Rectification
24 CC1092267A
[Indication] / Problem Possible cause Remedy
WARNING LINE PRESS
The LINE PRESS is larger than the DESIGN
PRESS + 0.5 bar (7 psi) and simultaneously
a load request was given via the RS485
interface.
Suppress load requests via the RS485
interface if the LINE PRESS is higher
than the DESIGN PRESS + 0.5 bar (7
psi).
Pressure and temperature
indicator failed, indicator (----)
Ground fault or short circuit for sensor B1N,
B2N or R1F
Check fuses, changing if necessary
FAULT VSD COMMUNIC.
Communication to inverter disrupted, inverter
not responding
Check , Main contactor and ModBus
interface wiring
If no fault can be found, notify
Hydrovane service engineer.
FAULT VSD FAULT xx
The inverter (VSD) detected a fault with error
number xx that was not subsequently listed.
Contact a Hydrovane Service Engineer.
FAULT VSD FAULT 1 Overvoltage on DC link
Check supply voltage is not above 500
volts
FAULT VSD FAULT 2
FAULT VSD FAULT 3
FAULT VSD FAULT 15
Undervoltage on DC link
Input Phase failure
Load-shunt relay has not energised
Check supply voltage
Check the supply cable, main contactor
poles, input choke and EMC filter for
high resistance and voltage drop.
FAULT VSD FAULT 4
Overcurrent.
Check for short circuit at the VSD
output.
Check the compressor motor is wired
correctly.
FAULT VSD FAULT 6
FAULT VSD FAULT 7
FAULT VSD FAULT 8
FAULT VSD FAULT 36
VSD Internal Overheat
VSD Internal Overheat Cleared
VSD Power module Overheat
VSD Power module Overheat Cleared
Check the starter enclosure filters are
not blocked.
Reduce the ambient temperature of the
cooling fan intake.
FAULT VSD FAULT 12 VSD Power Unit Failure Contact a Hydrovane service engineer.
FAULT VSD FAULT 16
FAULT VSD FAULT 17
FAULT VSD FAULT 30
VSD OVERLOAD
(unloads compressor)
VSD Overload Shutdown
VSD Overload Cleared
Motor Overload
The Hydrovane Pro has detected the VSD
OL-counter has reached 20%
Check for mechanical faults in the
compressor application.
Check the compressor motor is wired
correctly.
VSD configuration may have been
adjusted incorrectly
FAULT SPEED LOW
Speed is below permissible minimum speed.
Oil level too low.
Notify Hydrovane Service Engineer.
Check.
WRONG SERIAL NUMBER
The Hydrovane Pro has detected a VSD that
has not been programmed
Select the appropriate HV MODEL to
program the VSD
WRONG VSD MODEL
The Hydrovane Pro has detected a VSD that
is the incorrect model
Select the correct HV MODEL
(1) Unit-specific setting: see Section 3.4 [ LIMIT VALUES ] menu
(2) Individual setting: see Section 2.6 [ MAINTENANCE SCHED. ] menu
(3) Individual setting: see Section 3.5 [ OPTIONAL IN-/OUTPUTS ] menu
(4) Individual setting: see Section 3.1 [ CONTROL MENU] menu
(5) Individual setting: see Section 3.3 [ TIMER CONTROL ] menu