ibaCom-L2B-x-8 Manual
Issue 3.2 21
11.1.1 iba_0F01.gsd – 32 Integer Inputs
This mode is used to read up to 32 integer values and 32 digital signals from the
PROFIBUS (OUT 72 Bytes).
11.1.1.1 DP-Master Output data
OUTPUT DATA
Byte no. Offset
Contents Remark
1 0 Status not used
2 1 Status not used
3 2 Status not used
4 3 Status not used
5 4 7 6 5 4 3 2 1 0 Dig. outputs channel 0...7
6 5 15 14 13 12 11 10 9 8 Dig. outputs channel 8...15
7 6 23 22 21 20 19 18 17 16 Dig. outputs channel 16...23
8 7 31 30 29 28 27 26 25 24 Dig. outputs channel 24...31
9 8
MSB
10
LSB
nalog output channel 0
Integer (2 byte), Big Endian Motorola
11 10
MSB
12
LSB
nalog output channel 1
Integer (2 byte), Big Endian Motorola
12
nalog outputs in total:
32 Words (16-bit integer), Big Endian Motorola
71 70
MSB
72
LSB
nalog output channel 31
Integer (2 byte), Big Endian Motorola
11.1.1.2 DP-Master Input data
No inputs
11.1.1.3 GSD File
GSD filename Remark
iba_0F01.gsd Transfer as word (S7-300/400)
11.1.1.4 Applications
ibaPDA, ibaLogic, system coupling Simatic S7, TDC, Simadyn D