ibaCom-L2B-x-8 Manual
Issue 3.2 23
11.1.3 iba_0F04.gsd – 28 Real Inputs
This mode is used to read up to 28 real values and 32 digital signals from the
PROFIBUS (OUT 120 Bytes) from a Simatic S7 as PROFIBUS master. Due to limita-
tions of the S7 real data type only 28 values can be used.
11.1.3.1 DP-Master Output data
OUTPUT DATA
Byte no. Offset
Contents Remark
1 0 Status not used
2 1 Status not used
3 2 Status not used
4 3 Status not used
5 4 7 6 5 4 3 2 1 0 Dig. outputs channel 0...7
6 5 15 14 13 12 11 10 9 8 Dig. outputs channel 8...15
7 6 23 22 21 20 19 18 17 16 Dig. outputs channel 16...23
8 7 31 30 29 28 27 26 25 24 Dig. outputs channel 24...31
9 8
MSB
10
11
12
LSB
nalog output channel 0
Real (4 byte), Big Endian Motorola
13 12
MSB
14
15
16
LSB
nalog output channel 1
Real (4 byte), Big Endian Motorola
16
nalog outputs in total:
28 Longs (Real), Big Endian Motorola
117 116
MSB
118
119
120
LSB
nalog output channel 27
Real (4 byte), Big Endian Motorola
11.1.3.2 DP-Master Input data
No inputs
11.1.3.3 GSD File
GSD filename Remark
iba_0F04.gsd Transfer as double word (S7-300/400)
11.1.3.4 Applications
ibaPDA, ibaLogic, system coupling, Simatic S7, TDC, Simadyn D