EasyManua.ls Logo

IBM 11000 VA LCD 5U - Page 63

IBM 11000 VA LCD 5U
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
To remove input power to change the battery modules, complete the following
steps.
Note: Qualified personnel can replace internal batteries without shutting down the
UPS and without having to remove the UPS from the rack cabinet.
1. Press and hold the on/off button until the long beep ceases (approximately 3
seconds), and then disconnect the UPS.
2. Wait 60 seconds while the internal processor shuts down before you disconnect
the battery.
To replace the battery modules, complete the following steps:
1. Remove the UPS lower front bezel. Press the two side latches toward each
other to release the bezel, and pull the bezel away.
O
K
OK
1
0
0
%
6
m
i
n
2. Loosen the thumbscrew on the left battery retention bracket 1, slide the
bracket to the right 2, rotate the bracket out 3, and then remove it.
O
K
OK
1
0
0
%
6
m
in
L
Chapter 5. Hardware maintenance information 49

Table of Contents

Related product manuals