CONTAINERIZED KITCHEN (CK) 0010 00
TROUBLESHOOTING PROCEDURES (ELECTRICAL SYSTEM)
0010 00-2
Table 1. Troubleshooting Procedures (Electrical System) – Continued
Malfunction Test or Inspection Corrective Action
Ensure that the generator
power control circuit breaker
(Power Entrance Panel) is shut
(pushed in)
Notify unit maintenance
GENERATOR POWER
AVAILABLE indicator is lit,
GENERATOR POWER indicator is
not lit.
Press the GENERATOR
POWER pushbutton (Main
Control Panel)
Notify unit maintenance
GENERATOR POWER
AVAILABLE indicator is lit,
GENERATOR POWER indicator is
lit
Check/reset the input power
circuit breaker (#1 on Power
Distribution Panel).
Notify unit maintenance
Generator will not
crank
Check that the E-Stop (Main
Control Panel) is reset (pulled out)
Reset E-Stop
Check that DC control power circuit
breaker CB1 (behind generator
control panel) is reset (pushed in)
Reset circuit breaker
Check that the E-Stop circuit
breaker (Power Entrance Panel) is
reset (pushed in)
Reset circuit breaker
Check that the generator DEAD
CRANK switch is in NORMAL
(behind generator access door
accessible from inside the
mechanical room)
Place switch in NORMAL
Check generator battery
connections (inside access doors
on both sides of generator)
If loose or corroded, notify unit
maintenance
Generator cranks but
does not start
Check that the generator DEAD
CRANK switch is in NORMAL
(behind generator access door
accessible from inside the
mechanical room)
Place switch in NORMAL