TM 10-7360-226-13&P
CONTAINERIZED KITCHEN (CK) 0010 00
TROUBLESHOOTING PROCEDURES (ELECTRICAL SYSTEM)
0010 00-3/4 Blank
Table 1. Troubleshooting Procedures (Electrical System) - Continued
Malfunction Test or Inspection Corrective Action
Check generator fuel level Refill fuel tank
Check for dirty fuel filter/water
separator
Service fuel filter/water
separator (Refer to TM 9-6115-
642-10)
Check air cleaner restriction
indicator for indication of a clogged
air cleaner (inside access door by
cook center)
Service air cleaner assembly
(Refer to TM 9-6115-642-10)
Ambient temperature below 40
o
F Turn master switch (generator
control panel) to PREHEAT for
no more than 30 seconds
before cranking engine. Refer
to TM 9-6115-642-10
Notify unit maintenance
Interior lights do not
work
No other electrical components
operate
See “No Power to Kitchen”
All other electrical components
operate
Check/reset lighting circuit
breaker (#19 on Power
Distribution Panel)
Notify unit maintenance
No power at one or
more receptacles
No other electrical components
operate
See “No Power to Kitchen”
All other electrical components
operate properly
Check/reset ground fault
interrupter (on receptacle next
to spice rack)
Notify unit maintenance
END OF WORK PACKAGE