permitted) that re-directs the flue gas away by use of an elbow
or tee, certified to ULC S636 from the adjacent property line
must be used. (See Figure 44 and Figure 46)
The concentric vent kit currently cannot be modified to attach
an elbow to the vent portion of the rain cap. A tee attached to
the rain cap could potentially direct the flue gas plume toward
the intake air stream and contaminate the incoming combustion
air for the furnace.
Refer to Figure 44 and Figure 46 for terminations approved for
use in Alberta and Saskatchewan.
Figure 44 ITee at Termination Outlet
I
OPTIONALTERMINATION
BRACKETFOR2 PIPE
TERMINATIONS _
\
12-in
30.48 cm
Above anticipated
snow level
L12F030
Sample Inlet Air Pipe Connection
Figure 45 for Polypropylene Venting Systems
EXAMPLE FOR
UPFLOW INSTALLATIONS.
MAY BEAPPLIED TO
OTHERCONFIGURATIONS.
A12220
Figure 46 IVent Terminations
COMBUSTION AIR
(ELBOW PARALLEL
TO WALL)
J
SEPARATION
LEVEL OR GRADE,
WHICHEVER IS
GREATER
OVERHANG
Clearance to overhang per code
For single pipe vent
applications, install a 45
degree elbow pointing
......"'_ downward
L12F031
40 Specificationssubjectto change without notice. 440 01 4101 03