INSTALLATION
Ideal Logic + Combi - Installation and Servicing
FLUE OUTLET
21
ASSEMBLING THE ROOF FLUE KIT
Determine the correct height that the ue should terminate above
the roof. If after calculating or measuring the overall ue height
from the top of the boiler, it is necessary to cut both pipes of
assembly A, then ensure they are cut equally leaving the inner
ue tube longer than the outer air tube as supplied.
Ensure the cut pipe ends are free from any burrs.
1. Position the roof ashing plate (supplied separately) over the
hole cut in the roof and insert ue terminal from the roof end.
nm8739
min 16
o
max 41
o
MAX LENGTH:
7.5m
BOILER
nm8740
Flue Terminal
Pitched roof tile
weather collar
Flat roof tile
weather collar
1
3G9557b
'X'
6
2. Fit the vertical connector (supplied separately) in accordance with
the instructions provided with the vertical connector kit.
3. Secure the vertical connector by applying downward pressure on
the connector.
4. Position the clamp on the top face of the ue manifold and push
it horizontally backwards. Locate both clamp lugs into the ue
manifold and secure to the ue manifold with the M5 retaining
screw.
5. “Push” t extension duct (if required (supplied separately)) into
vertical connector.
Note. Ensure turret sample points are servicable and all caps and plugs
are tted.
6. If the last extension duct requires cutting, measure ‘X’, the distance
(outer ducts), between the duct and the terminal and add 100 mm to this
dimension. This gives the length of the last extension duct.
Note. Check the position of the inner ue duct relative to the outer duct
on the assembled extension duct(s) and ensure the terminal ue duct is
cut longer than the air duct to ensure engagement in the nal ue duct
seal.
7. Finally ensure the roof ashing plate is correctly sealed to the roof.
ASSEMBLY A
2
Extension
Duct
Vertical
connector
5
4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEAL LOGIC + Combi 24 and is the answer not in the manual?

IDEAL LOGIC + Combi 24 Specifications

General IconGeneral
ModelLOGIC + Combi 24
CategoryBoiler
Boiler TypeCombi
Fuel TypeNatural Gas
Output24 kW
Efficiency94%
Dimensions700 x 395 x 278 mm
Warranty7 years
Max Working Pressure3 bar
Central Heating Flow Temperature Range30 - 80 °C

Related product manuals