• [OFF]: The simulation is not active.
10.6.7.2 Parameter setting via IO-Link: simulation
u Select [Parameter] > [Simulation].
u Select [S.Tim] and set the time of the simulation in minutes.
u Select [Parameter] > [Simulation] > [Flow].
u Select [S.FLW] and set the flow value to be simulated or a fault condition (e.g. OL).
u Select [Parameter] > [Simulation] > [Temperature].
u Select [S.TMP] and set the temperature value to be simulated or a fault condition (e.g. OL).
u Select [Write to device].
w The changed values are transferred to the unit.
u Select [Parameter] > [Simulation].
u Execute command: [Start Simulation].
w The simulation starts with the set values.
u To end the simulation: Execute command: [Stop Simulation].
10.7 Identification
10.7.1 Device information
Unalterable device information is stored on the unit. This includes:
• Product name
• Product family
• Manufacturer
• Manufacturer ID
• Device ID
• Serial number
• Hardware / firmware revision
• Description
In addition, further freely definable tags with a maximum length of 32 characters can be assigned to
the unit via the IO-Link interface using suitable parameter setting software. This includes:
• application-specific tag
• function tag
• location tag
Read/edit device information:
u Select [Identification].
u Read device information or edit editable parameters.
10.7.1.1 Reading via the unit keys: device information
u Go to the [EF] > [d.InF] menu.
u Read the unit information.