Ultrasonic flow meter SU2020 SU8020 SU2021 SU8021 SU2621 SU8621
11
F
F
F
A
B
C
Fig.3: recommended installation position
F: direction of flow
A: horizontal installation, display on the side of the pipe.
B: horizontal installation, display on top of the pipe.
C: vertical installation.
The unit can be installed independently of the orientation if the following is ensured:
- No air bubbles can form in the pipe system.
- The pipes are always completely filled.
5.3.2 Non recommended installation position
Directly in front of a falling pipe.
In a falling pipe.
Directly in front of the spout of a pipe.
Directly in front of a valve.
On the suction side of a pump.
At the highest point of the pipe system.