EasyManuals Logo

Immergas INTEC 12 System External User Manual

Immergas INTEC 12 System External
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
13
INSTALLERUSER
MAINTENANCE TECHNICIAN
Error
Code
Anomaly signalled Cause Boiler status / Solution
24
Push button control
panel anomaly
e board detects an anomaly on the pushbutton panel
If normal conditions are restored the boiler
restarts without having to be reset (1).
25
Block due to ue gas
temperature gradi-
ent intervention
If the board detects a rapid increase in ue gas temperature probably due
to a blocked circulating pump or lack of water in the heat exchanger, the
boiler shuts down due to the ue gas temperature gradient trip.
Press the Reset button (1).
27
Insucient circula-
tion
is occurs if there is overheating in the boiler due to insucient water
circulating in the primary circuit; the causes can be:
- low system circulation; check that no shut-o devices are closed on the
heating circuit and that the system is free of air (deaerated);
- pump blocked; free the pump.
Press the Reset button (1).
29 Flue probe anomaly
If the board detects an anomaly on the ue gas probe the boiler will not
start
e boiler does not start (1).
31
Loss of remote con-
trol communication
is occurs 1 minute aer communication is lost between the boiler and
the remote control.
Power cycle the boiler. If the Remote
Control is still not detected on re-starting
the boiler will switch to local operating
mode, i.e. using the controls on the control
panel (1).
36
IMG Bus communi-
cation loss
Communication between the various components is interrupted due to
an anomaly on the boiler control unit, on the zone control unit or on
the IMG Bus.
e boiler does not satisfy the room heating
requests (1).
37
Low power supply
voltage
is occurs when the power supply voltage is lower than the allowed limits
for the correct boiler operation.
If normal conditions are restored the boiler
restarts without having to be reset (1).
38 Loss of ame signal
is occurs when the boiler is ignited correctly and the burner ame
switches o unexpectedly; a new ignition attempt is performed and if
normal conditions are restored, the boiler does not need to be reset (this
fault can be checked in the list of errors in the “Information” menu only).
If normal conditions are restored the boiler
restarts without having to be reset (1).
43
Block due to loss
of continue flame
signal
is occurs if the ''Flame signal loss'' error occurs many times in a row
within a preset period (38).
Press the Reset button, before restarting, the
boiler will run a post-ventilation cycle (1).
44
Block for exceeding
the maximum accu-
mulated time, close
gas valve opening
is occurs if the gas valve remains open for longer than required for
normal operation, without the boiler switching on.
Press the Reset button (1).
45 High T
If the board detects a sudden and unexpected rise in ΔT between the
system ow probe and return probe, the boiler limits the burner output
to prevent damaging the condensing module; when the correct ΔT has
been restored, the boiler returns to normal operation.
Make sure there is water circulating in the
boiler, that the pump is congured accord-
ing to system requirements and that the
return probe works properly (1).
46
Low temperature
safety thermostat
(optional)
During normal operation, if an anomaly causes excessive overheating of
the ow temperature in low temperature conditions, the boiler blocks.
In this case, aer suitable cooling, it is pos-
sible to reset the thermostat (see relative
instructions sheet) (1).
47
Burner power limi-
tation
Should ue high temperature be detected, the boiler reduces power sup-
plied so as not to damage it.
(1).
49
High temperature
block on return
probe
is occurs when the heat exchanger return circuit reaches too high of
a temperature.
Make sure that water circulates properly
in the boiler and that the three-way valve
works properly. To eliminate it, the Reset
button (C) must be pressed (1).
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Technical Aer-Sales Service).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Immergas INTEC 12 System External and is the answer not in the manual?

Immergas INTEC 12 System External Specifications

General IconGeneral
BrandImmergas
ModelINTEC 12 System External
CategoryBoiler
LanguageEnglish

Related product manuals