52
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
3.9 P.C.B. PROGRAMMING
e boiler is prepared for possible programming of several opera-
tion parameters.
By modifying these parameters as described below, the boiler can
be adapted according to specic needs.
To access the programming phase, proceed as described below
(Parag 2.3):
- press buttons ( ) and ( ) for 5 about seconds until the
programming mode is accessed on the display;
- using buttons ( ) and ( ), select the parameter to be changed
indicated in the following table;
- adjust the corresponding value consulting the table using but-
tons ( ) and ( );
- conrm the value set by pressing the button ( ) for about 5
seconds.
2 minutes aer no button is touched will automatically
cancel the operation or by pressing buttons
( ) and ( ) simultaneously for about 5 se-
conds.