iDrive2 inverters Function Parameters
31
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P02.02
Asynchronou
s motor rated
frequency
0.01Hz~P00.03 (the Max. frequency)
50.00Hz
P02.03
Asynchronou
s motor rated
speed
1~36000rpm
Depend
on model
P02.04
Asynchronou
s motor rated
voltage
0~1200V
Depend
on model
P02.05
Asynchronou
s motor rated
current
0.8~6000.0A
Depend
on model
P02.06
Asynchronou
s motor
stator
resistor
0.001~65.535Ω
Depend
on model
P02.07
Asynchronou
s motor rotor
resistor
0.001~65.535Ω
Depend
on model
P02.08
Asynchronou
s motor
leakage
inductance
0.1~6553.5mH
Depend
on model
P02.09
Asynchronou
s motor
mutual
inductance
0.1~6553.5mH
Depend
on model
P02.10
Asynchronou
s motor
non-load
current
0.1~6553.5A
Depend
on model
P02.26
Motor
overload
protection
0:No protection
1: Common motor (with low speed compensation).
Because the heat-releasing effect of the common motors
will be weakened, the corresponding electric heat
2