Operating Manual
D-TEK
®
3
Refrigerant Leak Detector
English · Español · Deutsch · Français · Italiano · 中文 ·日本語 · Pyccĸий·
Polski · Svenska · Türkçe · Nederlands · 한국어 · Český
074-710-P16A

Table of Contents

Questions and Answers

  • A
    adamlongAug 18, 2025
    Why my Inficon Security Sensors unit turns on, but does not detect refrigerant?
    • J
      James BensonAug 18, 2025
      There are several reasons why your Inficon Security Sensors unit might not be detecting refrigerant: * The unit may not have completed warm-up. Allow 45 to 90 seconds for warm-up to complete. * The filter could be clogged. Replace the filter cartridge. * The pump may have failed. Listen for the pump sound; if there's no sound and the battery is charged, contact INFICON. * The sensitivity might be set too low (Pinpoint mode only). Verify the sensitivity level, using High or Super for small leaks. * The incorrect sensor might be installed. Ensure the correct sensor (refrigerant or CO sensor) is being used.
  • K
    Kristen ThomasAug 20, 2025
    What to do if all leak indicators flash on Inficon D-TEK 3 Security Sensors?
    • U
      ustewartAug 21, 2025
      If all leak indicators are flashing on your Inficon Security Sensors unit, it indicates a sensor error. This can be due to a failed sensor, improper sensor installation, or a poor connection. Remove and reinstall the sensor. If the problem is not fixed, replace the sensor.
  • N
    Nicole HarperAug 22, 2025
    Why is my Inficon Security Sensors unit not detecting refrigerant?
    • M
      Michael HoustonAug 23, 2025
      There could be several reasons why your Inficon Security Sensors unit isn't detecting refrigerant: 1. The unit may not have completed its warm-up cycle, which takes 45 to 90 seconds. Wait for the warm-up to complete. 2. The filter might be clogged, restricting airflow. Replace the filter cartridge. 3. The pump may have failed. Listen for the pump sound; if there's no sound and the battery is charged, contact INFICON. 4. The sensitivity might be set too low in Pinpoint mode. Verify the sensitivity level, and use High or Super for very small leaks. 5. The incorrect sensor might be installed. Ensure that the correct sensor (refrigerant sensor or CO sensor) is being used.
  • H
    heather92Aug 26, 2025
    What to do if the Inficon Security Sensors indicators do not turn on?
    • H
      Heather ParkAug 26, 2025
      If the indicators on your Inficon Security Sensors unit do not turn on after long-pressing the power button, the battery level is likely critically low. Charge the battery or plug the unit into a charger.
  • B
    bellalanAug 28, 2025
    How to fix Inficon D-TEK 3 power indicator quickly flashes red?
    • E
      erinparsonsAug 28, 2025
      If the power indicator on your Inficon Security Sensors unit is quickly flashing red, it indicates a battery error. This can occur due to a failed battery, improper battery installation, or a poor connection. Try removing and reinstalling the battery. If the problem persists, replace the battery. Another cause might be that the battery is outside the ideal temperature range. Allow the battery to return to normal temperature.
  • C
    carterjosephAug 30, 2025
    Why does my Inficon Security Sensors unit alarm in clean air?
    • W
      William RobertsAug 30, 2025
      If your Inficon Security Sensors unit is alarming in clean air, it's possible that the incorrect sensor is installed. Verify that the refrigerant sensor is installed instead of the CO 2 sensor.
  • R
    rmccannSep 2, 2025
    Why is the pump not making a sound in my Inficon D-TEK 3 unit?
    • A
      alisonhillSep 2, 2025
      If the pump in your Inficon Security Sensors unit is not making a sound, it suggests that the pump has failed. If the battery has a proper charge, contact INFICON.
  • C
    Cristina CarterSep 4, 2025
    What to do if the power indicator quickly flashes red on Inficon Security Sensors?
    • A
      Alison ChanSep 4, 2025
      If the power indicator on your Inficon Security Sensors is flashing red, it could be due to a battery error. This can be caused by a failed battery, improper installation, or a poor connection. Try removing and reinstalling the battery. If the problem persists, replace the battery. Another possible cause is that the battery temperature is outside the ideal range. Allow the battery to return to normal temperature.
  • C
    Christopher OdomSep 6, 2025
    Why won't the Inficon D-TEK 3 Security Sensors indicators turn on?
    • C
      Christina AllenSep 7, 2025
      If the indicators on your Inficon Security Sensors don't turn on after pressing the power button, the battery level is likely critically low. Charge the battery or plug the unit into a charger.
  • J
    Joseph DavisSep 9, 2025
    Why does my Inficon D-TEK 3 alarm in clean air?
    • A
      akennedySep 9, 2025
      If your Inficon Security Sensors unit is alarming in clean air, it's possible that the incorrect sensor is installed. Verify that the refrigerant sensor is installed instead of the CO 2 sensor.

Summary

Declaration of Conformity

Cautions and Warnings

General Cautions

Provides general precautions for using the D-TEK 3 refrigerant leak detector.

Operating Warnings

Highlights critical warnings related to operating the device and its battery.

Health Hazard Warnings

Details dangers of exposure to high concentrations of CO2 or refrigerants.

Explosion Hazard Warnings

Warns against using the product in potentially explosive environments.

Specifications

General Technical Specifications

Details usage, sensor types, battery, charging, and environmental parameters.

EN 14624 Compliance

Specifies sensitivity, response time, and zeroing for refrigerants per EN 14624.

SAE Application Guidelines

Lists sensitivity settings for SAE standards and chemicals that may cause false triggers.

SAE Leak Test Procedure

Details the recommended procedure for leak testing according to SAE standards.

Patents Information

Mentions pending patent applications related to the device.

D-TEK 3 Overview

Device Controls and Indicators

Identifies key controls like MODE, SENS/ZERO buttons, and indicators on the device.

Battery Compartment Access

Shows how to access the battery compartment via the eject button.

Device Side Views and Ports

Illustrates the device's side profile, including power and I/O ports.

Charging the Battery

Battery Charge Indicators

Explains the color codes (Green, Orange, Red) for battery charge status.

Charging Usage Note

States that the D-TEK 3 can be used while it is charging.

Powering On and Preparation

Powering On;Off

Instructions for turning the D-TEK 3 unit on and off using the power button.

Warm-up Procedure

Describes the device's warm-up period and when it's ready for use.

Mode Switching

Explains how to switch between Pinpoint and Manual Zero modes using the MODE button.

Pinpoint Mode Operation

Locating Suspected Leaks

Guides on positioning the probe near leaks and moving it slowly to detect them.

Leak Identification and Verification

Details how to confirm a detected leak and reset the zero point.

Sensitivity Adjustment

Explains how to adjust sensitivity for pinpointing leaks of different sizes.

Manual Zero Mode Operation

Manual Zeroing Process

Describes how to manually set the zero point and interpret the MODE indicator.

Manual Zero Mode Characteristics

Explains the audible cues and lack of sensitivity settings in Manual Zero mode.

Manual Zero Warm-up

Notes the requirement for an extended warm-up time for optimal performance.

Audio Features

Headphone Jack Usage

Details the headphone jack location and a warning about using non-INFICON headphones.

Volume Control

Explains how to use the volume button to adjust sound levels or mute the device.

Battery Management

Removing the Battery

Provides step-by-step instructions for removing the lithium-ion battery from the device.

Installing the Battery

Details the correct procedure for inserting and securing the lithium-ion battery.

Sensor Replacement

Sensor Removal Procedure

Outlines the process for removing the existing sensor using the eject button and release tab.

Sensor Installation Procedure

Describes how to install a new sensor, aligning it with the rails and securing it.

Filter Maintenance

Filter Function and Replacement

Explains the purpose of the hydrophobic filter and how to replace it.

Filter Handling Caution

Warns against operating the instrument without a probe tip and filter.

Extra-long Probe Accessory

Installing the Extra-long Probe

Guides on how to install the optional extra-long probe for hard-to-reach areas.

Needle Probe Extension Accessory

Installing the Needle Probe Extension

Details the installation of the needle probe extension for tight spots and insulation.

Optional Sensors

Sensor Type Recognition

Explains how the device recognizes CO2 and flammable refrigerant sensors via indicator colors.

Flammable Sensor Limitations

States that the flammable refrigerant sensor does not detect hydrogen or hydrogen forming gas.

CO2 Leak Detection Precautions

Advises wearing a respirator or mask when searching for CO2 leaks.

General Safety Warnings for Sensor Use

Reiterates warnings about hazardous environments and exposure to refrigerants.

Intrinsically Safe Warning for Sensor Use

Warns against using the product in explosive atmospheres due to it not being intrinsically safe.

Cleaning and Storage

Cleaning Instructions

Provides guidelines on cleaning the instrument using mild detergent or isopropyl alcohol.

Cleaning Solvents to Avoid

Lists aggressive solvents like gasoline and acetone that should not be used for cleaning.

Replacement Parts and Accessories

Accessory List

Lists various replacement parts and accessories available for the D-TEK 3.

Troubleshooting Guide

Power Indicator Issues

Addresses problems with the power indicator flashing red and potential causes/remedies.

Leak Indicator Issues

Troubleshoots issues where all leak indicators flash, relating to sensor or battery.

No Power;Detection Issues

Solves problems with the unit not turning on or not detecting refrigerant after warm-up.

False Alarm;Detection Issues

Helps diagnose false alarms, clogged filters, pump failures, and incorrect sensor installation.

Alarm and Pump Issues

Addresses alarms in clean air and problems with the pump not operating correctly.

Warranty and Liability

Product Warranty Terms

Details the warranty period, exclusions for normal wear items, and conditions for claims.

Liability Limitations

Outlines INFICON's limitations on liability for damages, including incidental and consequential.

Inficon D-TEK 3 Specifications

General IconGeneral
Operating Temperature32°F to 122°F (0°C to 50°C)
Weight1.5 lbs (0.68 kg)
Response TimeInstantaneous
Warranty1 year
Sensitivity0.1 oz/yr (3 g/yr)
RefrigerantsCFC, HCFC, HFC