E4
Evolution
II + 10 k
TT (S)
E4
Evolution
II + 15 k
TT (S)
E4
Evolution
II + 20 k
TT (S)
E4
Evolution
II + 30 k
TT (S)
E4
Evolution
II + 40 k
TT (S)
E4
Evolution
II + 60 k
TT S
E4
Evolution
II + 80 k TT
S
110 VAC(Ph-N) ± 3 % at 50% Load; 176 VAC(Ph-N) ± 3 % at 100% Load
Low Line Loss Voltage + 10V
300 VAC(L-N) ± 3 % at 50% Load; 276 VAC(L-N) ± 3 % at 100% Load
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
360/380/400/415VAC (Ph-Ph)
208*/220/230/240VAC (Ph-N)
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system;
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
9 hours recover to 90% capacity
2.0 A ± 10% (Recommended)
1.0~12.0A (Adjustable)
Depending on applications
1.0~12.0A ±10% (Adjustable)
2.0~24.0A ±10%
(Adjustable)
+/- 13.65 VDC * N ± 1% (N = 16~20)
Dimension, D X W
X H (mm)
0 ~ 40°C (the battery life will down when > 25°C)