EasyManua.ls Logo

INFOSEC UPS SYSTEM E4 Evolution II + TT Series - Lcd Setting

INFOSEC UPS SYSTEM E4 Evolution II + TT Series
185 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
87
INFOSEC UPS SYSTEM 15, rue du Moulin 44880 Sautron France www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 fax : +33(0)2 40 94 29 51 hotline@infosec.fr 07 19 AA 59 205 03

There are three parameters to set up the UPS. Refer to diagram 13.
 is for program alternatives. There
are 20 programs to set up. Refer to the table
below.
 are the setting
options or values for each program.
Select “Up” or “Down” buttons to
change the programs or parameters.










01
Output voltage
Y*
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
ECO mode enable/disable
Y
06
Voltage range for ECO mode
Y
07
Frequency range for ECO mode
Y
08
Bypass mode setting
Y
Y
09
Maximum battery discharge time setting
Y
Y
Y
Y
Y
Y
10
Reserved
Reserved for future options
11
Hot standby function Setting
Y
12
Neutral loss detection
Y
Y
Y
Y
Y
Y
13
Battery voltage calibration
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
Inverter A voltage adjustment
Y
Y
Y
16
Inverter B voltage adjustment
Y
Y
Y
17
Inverter C voltage adjustment
Y
Y
Y
18
Output A voltage calibration
Y
Y
Y
19
Output B voltage calibration
Y
Y
Y
20
Output C voltage calibration
Y
Y
Y
*Y (YES) means that this program can be set in this mode.
 All parameter settings will be saved only when UPS shuts down normally with internal or external
battery connection. (Normal UPS shutdown means turning off input breaker in bypass/no output mode).

LCD Settings
Parameter 1
Parameter 2
Parameter 3

Table of Contents

Related product manuals