EasyManua.ls Logo

INFOSEC UPS SYSTEM E4 Evolution II + TT Series - Operating Mode;Status Description

INFOSEC UPS SYSTEM E4 Evolution II + TT Series
185 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
92
INFOSEC UPS SYSTEM 15, rue du Moulin 44880 Sautron France www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 fax : +33(0)2 40 94 29 51 hotline@infosec.fr 07 19 AA 59 205 03
 it always shows  as output voltage.
  it shows the internal measurement value of the
output A voltage, and you can calibrate it by pressing  or 
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing . The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.



 it always shows  as output voltage*.
  it shows the internal measurement value of the
output B voltage, and you can calibrate it by pressing  or 
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing . The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
*It will display number 1 under to represent the output B
voltage.



 it always shows  as output voltage.
  it shows the internal measurement value of the
output C voltage, and you can calibrate it by pressing  or 
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing . The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
*It will display number 2 under to represent the output C
voltage.

Following table shows LCD display for operating modes and status.
(1) If the UPS is in normal operation, it will show seven screens one by one, which represents 3 phase input
voltages (An, bn, Cn), 3 line input voltages (Ab, bC, CA) and frequency in turns.
(2) If parallel UPS systems are successfully set up, it will show one more screen with “” in parameter 2
and assigned number in parameter 3 as below parallel screen diagram. The master UPS will be default
assigned as ” and slave UPSs will be assigned as either “002” or “003”. The assigned numbers may be
changed dynamically in the operation;


UPS Power
On
Description
When UPS is powered on, it will enter into this mode for a few seconds as
initializing the CPU and system.

Table of Contents

Related product manuals