INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel: +33 (0)2 40 76 15 82 – fax: +33(0)2 40 94 29 51 – hotline@infosec.fr – 11 12 AA 59 203 06
E6 LCD RT
EVOLUTION (S) 1000
E6 LCD RT
EVOLUTION (S) 2000
E6 LCD RT
EVOLUTION (S) 3000
On Line Double Conversion
TECHNICAL INPUT CHARACTERISTICS
[80 / 70 / 60 / 55 VAC ± 5 %] or [160 / 140 / 120 / 110 VAC ± 5 %]
(based on load % : 100%-80% / 80%-70% / 70%-60% / 60%-0)
[85 / 75 / 65 / 60 VAC ± 5 %] or [170 / 150 / 130 / 120 VAC ± 5 %]
150 VAC ± 5 % or 300 VAC ± 5 %
140 VAC ± 5 % or 290 VAC ± 5 %
TECHNICAL OUTPUT CHARACTERISTICS
[110/115/120/127 VAC] or [208/220/230/240 VAC]
Voltage regulation (battery mode)
Frequency range (synchronized)
Frequency range (battery mode)
50Hz ± 0.5% or 60Hz ± 0.5%
Harmonic distortion (THDU)
≦ 2% (linear load)
8% max (battery mode before shut down)
From 4 to 30 min. depending on connected load
IEC type
standard/programmable
3 /3 (10A)
+ 1 standard (16A)
NEMA type
standard/programmable