Installation manual
Installation 31
3-1-4
Thermal probe
The thermal probe [D] optimizes the battery charge process. This device regulates the
charging process in accordance with the battery temperature. The thermal probe protects
against battery overheating and consequent permanent damage to the battery.
To connect a thermal probe, work through the following steps.
1. Disconnect the battery (if necessary).
2. Connect the thermal probe to the connector on the power supply [E] (Table 2-5: Con-
trol panels - description of parts, D).
3. Attach the thermal probe to the battery[F], in such a way as to provide optimized heat-
transfer measurements.
3-1-5
Opening and closing the control panel
If you wish to remove the metal frontplate, work carefully through the following steps.
1. Type-in the installer code on the keypad and press OK. Access to the installer menu
inhibits the activation of the output and any report calls associated with the “Open-
panel” event.
2. Remove the 2 screws and the metal frontplate.
3. Insert the Maintenance jumper (refer to paragraph 3-1-9 Maintenance status) and carry
out the necessary work.
Once your task is complete, work carefully through the following steps.
1. Remove the Maintenance jumper.
2. Using the 2 screws, secure the frontplate in place.
3. Exit the Installer menu.