5 Parameter Table
- 33 -
Para� No� Para� Name Setting Range Unit Default Property
Group F8: Auxiliary Functions
F8-17 Preset running time 0 to 65000 h 1 h 0 h
☆
F8-18 Protection enable upon startup 0: Disable
1: enable
1 0
☆
F8-22 Ground fault detection enable upon
power on
0: Disable
1: enable
1 1
☆
F8-23 Selection for reactions of preset
running time out
0: Disable
1: enable
1 0
☆
F8-24 Undervoltage level(the voltage of
input)
148�5 to 321�7 V 0�1 V 247�5 V
☆
F8-25 Braking operation duration limit 0�0s to 3600�0s 0�1s 5�0s
☆
F8-26 Braking resistor protection 0: Disable
1: enable
1 1
☆
F8-27 Output ground fault protection upon
starting
0: Disable
1: enable
1 0
☆
F8-28 Output phase loss protection upon
starting
0: Disable
1: enable
1 1
☆
F8-29 Braking resistor overload protection 0: Disable
1: enable
0 to 1 1
☆
Group F9: Protection and Fault
F9-00 Motor overload protection 0: disable
1: enable
1 0
☆
F9-01 Motor overload protection factor 0�20 to 10�00 0�01 2�00
☆
F9-08 Braking level 700 to 800 V 1 V 750 V
☆
F9-12 Input phase loss detection enable 0: disable
1: enable
1 1
☆
F9-13 Output phase loss detection enable 0: Disable
1: enable
1 1
☆
F9-14 Speed error protection threshold 0�50 to 50�00 Hz 0�01 Hz 10�00 Hz
☆
F9-15 Speed error protection time 0�0s to 20�0s 0�1s 10�0s
☆
F9-16 Motor temperature protection enable 0: Disable
1: enable
1 1
☆