MD280/MD280N User Manual                                            Safety and Precautions 
15
If a contactor is installed between the power supply and the input terminal 
of the inverter, it is not allowed to use the contactor to control the 
startup/stop of the inverter. If use of such contactor is unavoidable, it shall 
be used with interval of at least one hour. Frequent charge and discharge 
will reduce the service life of the capacitor inside the inverter.    If switching 
devices like contactor are installed between the output end of the inverter 
and the motor, it shall ensure that the on/off operation is conducted when 
the inverter has no output. Otherwise the modules in the inverter may be 
damaged.  
1.2.8 Use under voltage rather than rated voltag 
If the MD series inverter is used outside the allowable working voltage 
range as specified in this manual, it is easy to damage the devices in the 
inverter.  When necessary, use the corresponding step-up or step-down 
instruments to change the voltage. 
1.2.9 Change Three-phase Input to Two-phase Input 
It is not allowed to change the MD series three-phase inverter into 
two-phase one.    Otherwise, it may cause fault or damage to the inverter.   
1.2.10 Lightning Impulse Protection 
The series inverter has lightning over current protection device, and has 
certain self-protection capacity against the lightning.  In applications 
where lightning occurs frequently, the user shall install additional protection 
devices at the front-end of the inverter.   
1.2.11 Altitude and Derating 
In areas with altitude of more than 1,000 meters, the heat sinking effect of 
the inverter may turn poo rer due to rare air. Therefore, it needs to derate 
the inverter for use. Please contact our company for technical consulting in 
case of such condition.      
1.2.12 Certain Special Use 
If the user needs to use the inverter with the methods other than the 
recommended wiring diagram in this manual, such as shared DC bus, 
please consult our company. 
1.2.13 Cautions of Inverter Disposal 
The electrolytic capacitors on the main circuit and the PCB may explode 
 