MD280/MD280N User Manual Parameter Description
- 157 -
Setup running time
Factory
default
value
0h
0h Invalid
F5-12
Setup
range
1h to 65535h Valid
It is used to set the time for the inverter to perform timing running. If the
running time is set to 0, this function is invalid.
When the accumulated running time (F7-12) reaches this set running time,
the digital output terminal DO outputs the signal of running time arrival.
Refer to the description of “Running Time Arrival” of DO output terminal in
Group F3.
Remark: If it does not perform timing running, please set the “Setup
Running Time” to 0.
Action selection at the
arrival of running time
Factory default
value
0
0: Continue to run
F5-13
Setup
range
1˖ Stop
It is the action performed by the inverter when the accumulated running
time (F7-12) reaches the setup running time (F5-12).
If the accumulated running time is larger or equal to the setup running time
and the running time arrival action is selected as “Stop”, the inverter will
report ERR26 fault, indicating that the running time is reached and the
inverter cannot start running. This fault cannot be reset and the inverter
cannot run until setting is performed according to the following three ways:
1) Select the running time arrival action as “Continue to run”.
2) Set the setup running time (F5-12) to “0h” and cancel the timing
function.
3) If timing remains, set the setup running time (F5-12) to a timing
duration that is higher than the accumulated running time (F7-12).
Caution: If it does not perform timing running, please set this parameter
value to “Continue to Run”.
Startup protection
selection
Factory
default value
0
0 Valid
F5-14
Setup
range
1 Invalid