Parameter Description MD280/MD280N User Manual
- 184 -
Please adjust this parameter according to the load inertia and weight.
Voltage (V)
Bus Voltage
utput Frequency
Setup Frequency
Acceleration Time 1 or
Acceleration Time 2
Time
Time
Voltage (V)
Bus Voltage
utput Frequency
Setup Frequency
Acceleration Time 1 or
Acceleration Time 2
Time
Time
Fig6-23 Schematic Diagram for Instantaneous Stop non-stop Running
Fault auto reset
times
Factory default
value
0
FB-13
Setup range 0 to 10
When the inverter selects fault auto reset, it is used to set the times of auto
reset. If this value is exceeded, the inverter will perform fault protection.
Caution:
1) Auto fault reset will not reset the external faults and running time
arrival fault automatically.
2) If the fault is reset manually, it will clear the times of auto reset to
zero.
Fault relay action
selection during fault
auto reset period
Factory default
value
0
0˖ No action
FB-14
Setup
range
1˖ Action
Select whether the fault relay
outputs fault alarm signal
during fault auto reset period
Fault auto reset interval
Factory default
value
1.0s
FB-15
Setup
range
0.1s to 60.0s
The waiting time of the
inverter from the fault alarm to
auto reset.
FB-16
Fault auto reset times
checkout time
Factory default
value
1.0h