MD280/MD280N User Manual Parameter Description
- 185 -
Setup
range
0.1h to
1000.0h
When the inverter runs for the
setup time of this parameter and
has no fault, it will clear the times
of auto reset to zero.
Input phase fault protection
selection
Factory
default
value
1
0˖ Invalid
FB-17
Setup range
1˖ Valid
MD280 series inverter above 18.5kW has input phase fault protection
function.For the inverter below 18.5kW (including 18.5kW) inverter, the
input phase fault protection function invalid.
Output phase faultprotection
selection
Factory
default value
1
0˖Invalid
FB-18
Setup
range
1˖Valid
Inverter module radiator
temperature
Factory default
value
-
FB-19
Setup
range
-10ć to 100ć
Display the Inverter
module temperature
FB-20 The first fault type
FB-21 The second fault type
FB-22 The last fault type
0 to 41
It records the latest 3 fault types for the inverter: 0 means no fault and 1 to
41 correspond to ERR01 to ERR41.Refer to Chapter 8 for the details.
FB-23
Frequency
upon fault
Display the frequency upon
the latest fault
FB-24
Current upon
fault
Display the current upon
the latest fault
FB-25
Bus voltage
upon fault
Display the frequency upon
the latest bus fault