Control command input to inverter (write-only) 
Command word 
address
Command function
0001˖ Forward operation 
0002˖ Reverse operation 
0003˖ Forward jog 
0004˖ Reverse jog 
0005˖ Free stop 
0006˖ Speed-down stop 
0007˖ Fault reset 
0100˖  Restore factory default value 
2000H 
0101˖  Clear the record information 
Caution: 
For 0100H ˄restore the factory value˅and 0101H (clear the recorded 
information),which must be removed the password locking,please refer to the 
parameter locking password check (4000H command addr. ). 
If there is user password (FP-00 is not zero), write the correct user password 
for 4000H command address.If there is no user password (FP-00 is zero), 
write zero to remove password locking for 4000H command address. 
After the host computer is unlocked, it gets the right of the communication 
restore the factory default value and communication clear the record 
information.If there is no communication within 5 minutes,the access right is 
invalid.Re-unlock so as to get the access right. 
Read inverter status :( Read-only) 
Status word address Status word function
0001˖ Forward rotation
0002˖ Reverse rotation
3000H 
0003˖ Stop 
Parameters locking password check: (If the return is the 8888H, it indicates 
the password checksum pass) 
Password address Contents of input password
4000H ***** 
Parameter locking command :( Write-only) 
Address of locking 
password command
Contents of locking password command
5000H 
0001˖  Locking system command code 
 