- 224 -
Inverter fault address Inverter fault information
0016˖ Reserved
0017˖ Earth short circuit fault
0018˖ Reserved
0019˖ Reserved
001A˖ Running time arrival fault
001F˖ Software over current fault
0028˖ Fast current limiting
0029˖ Swithing motor fault
Descriptive data of communication fault information (fault code)
Communication fault
address
Fault function description
8001H
0000˖ No fault
0001˖ Password error
0002˖ Command code error
0003˖ CRC check error
0004˖ Invalid address
0005˖ Invalid parameter
0006˖ Parameter change invalid
0007˖ The system is locked
0008˖ Being restoring parameters
6
ǃ
Group FA Communication Parameter Description
FA-00 Baud rate Factory
default value
5
0 300BPS
1 600BPS
2 1200BPS
3 2400BPS
4 4800BPS
5 9600BPS
6 19200BPS
Setup
range
7 38400BPS
This parameter is used to set the the data transfer rate between the host
computer and the inverter.
Caution: The baud rate of the host computer and the inverter must be
consistent.Otherwise, communication is impossible. The higher baud rate is,
the faster communication is.