Data format  Factory 
default value
0 
0 No check:data format<8,N,2> 
1  Even parity check :data format 
<8,E,1> 
FA-01 
Setup 
range 
2  Odd parity check : data 
format<8,O,1> 
When use the parity or odd parity, the length of each byte is 11 bits, which 
includes a start bit, 8 data bits, 1 parity bit and one end bit. 
When use the no check, the length of each byte is 11 bits, which includes a 
start bit, 8 data bits, 1 parity bit and 2 end bits. The data format of the host 
computer and the inverter setup must be consistent, otherwise, 
communication is impossible. 
Local addr. 
Factory  
default value 
1 
FA-02 
Setup range  0 to 247,0 is broadcast address 
The function code used to identify the local address of the inverter.The local 
address is unique (except the broadcast address), which can realize the 
broadcast function of host computer. 
Caution: When the local address is set to zero, that is the broadcast address, 
which can only receive and perform the broadcast address of host computer 
but not respond to the host computer. 
 
Response delay  Factory default 
value 
2ms 
FA-03 
Setup range  0 to 20ms 
Response delay: It refers to the interval time from the inverter finishes 
receiving data to sending data to the host machine.If the response delay is 
less than the system processing time, then the response based on the time 
delay of the system processing time.If the response delay is more than the 
system processing time, after the system processes the data, it should be 
delayed to wait until the response delay time is up, then sending data to host 
machine. 
 
 
 
 
 
 