Mechanical and Electrical Installation                               MD280/MD280N User Manual 
- 56 -
2˅Function Description of Control Terminal   
Table 3-3 Function Description of MD280 Inverter Control Terminal   
Type  Terminal 
Terminal 
Name
Function Description 
+10V-GND 
External 
terminal of 10V 
power supply 
Provide +10V power supply for external units, 
with maximum output current of 10mA.   
It is generally used as the operating power 
supply for the external potentiometer.   
The potentiometer resistance range is 1kȍ to 
5kȍ. 
Power supply 
+24V-COM 
External 
terminal of 24V 
power supply 
Provide +24V power supply for external units. It 
is generally used as the operating power supply 
for digital input/output terminal and the external 
sensor.  
Maximum output current: 200mA 
AI1-GND 
Analog input 
terminal 1 
1. Input voltage range: DC 0V to 10V (can be 
customized as non-standard -10VDC to 
+10VDC) 
2. Input impedance: 20kȍ 
Analog 
input 
AI2-GND 
Analog input 
terminal 2 
1. Input voltage range: DC 0V to 10V (can be 
customized as non-standard -10VDC to 
+10VDC)/0mA to 20mA, the selection of which 
depends on jumper J1 on the control panel.   
2. Input impedance: 20kȍ at the time of voltage 
input; 500ȍ at the time of current input.   
3. Keyboard potentiometer input: It can switch 
between AI2 and external keyboard 
potentiometer via Jumper J2. 
DI1-COM 1Digital Input 1
DI2-COM  Digital Input 2 
DI3-COM  Digital Input 3 
DI4-COM Digital Input4 
1. Optical coupling isolation.   
2. Input impedance: 3.3kȍ 
Digital 
Input 
DI5-COM 
High-speed 
pulse input 
terminal 
In addition to the characteristics of DI1 to DI4, it 
can also be used as the high-speed pulse input 
channel.  
Maximum input frequency: 50kHz. 
 
efesotomasyon.com