MD280/MD280N User Manual                                Mechanical and Electrical Installation 
- 57 -
Type  Terminal 
Terminal 
Name
Function Description 
Analog 
output 
AO-GND 
Analog Output 
1  
The voltage or current output is determined by 
jumper J3 on the control panel.   
Output voltage range: 0V to 10V 
Output current range: 0mA to 20mA. 
 
Type  Terminal 
Terminal 
name
Function description 
DO1-COM  
DO2-COM 
Digital output 
 
Optical coupling isolation,dual polarity open 
collector output 
Output voltage range: 0V to 24V 
Output current range: 0mA to 50mA
 
Digital 
Output 
FM-COM 
High-speed 
pulse output   
When it is used as high-speed pulse outputˈthe 
maximum frequency can reach 50kHz; 
When it is used as open collector output, it is the 
same as DO1 in terms of specification. 
Caution:The function of AOˈFMˈDO3 share the 
channel,only one of which can be selected. 
T/A-T/B 
Normally 
closed terminal
Relay 
output 
T/A-T/C 
Normally open 
terminal 
Contact driving capacity:   
AC250V,3A,COSij=0.4DŽ 
DC 30Vˈ1A 
A+/A- 
485  
communication 
port 
Standard 485 interface 
Auxiliary 
interface 
Keypad 
External 
keyboard 
interface 
Standard RJ45 network cable interface, used to 
provide signals for the external keyboard. 
 
3) Description of wiring of control terminals:   
    A. Analog input terminal:  
    Because the weak analog signal will be easily affected by the 
external interference, generally shielded cable shall be used, and the cable 
length shall be as short as possible and no longer than 20 meters, as 
shown in Fig.3-9, In case the analog signal is subject to severe interference, 
 