MD280/MD280N User Manual Function Parameter Table
- 69 -
Function code Name Setup Range
Minimu
m Unit
Factory
Default
Value
Change
Group F0 Basic function group
F0-00
Comma
nd
source
selection
0: Operation panel control channel
(LED ON)
1: Terminal command channel
(LED OFF)
2. Serial port communication
control channel (LED FLASHING)
1 0 ƿ
F0-01
Frequen
cy
source
selection
0: Digital setting (UP and Down
adjustment)
1: AI1
2: AI2
3: PULSE setting (DI5)
4: MS speed
5˖PLC
6˖PID
7˖AI1+AI2
8˖Communication setup
9˖PID + AI1
10˖PID + AI2
1 0 ƾ
F0-02
Digital
setup
frequenc
y
memory
selection
0:Without memory
1:Power fault memory
2:Stop memory
3:Stop and power fault memories
1 0 ƿ
F0-03
Pre-set
frequenc
y
0.00Hz to maximum frequency
(F0-04)
0.01Hz 50.00Hz ƿ
F0-04
Maximu
m
50.00Hz to 630.00Hz 0.01Hz 50.00Hz ƾ