MD280/MD280N User Manual Function Parameter Table
- 89 -
Function code Name Setup Range
Minimu
m Unit
Factory
Default
Value
Change
control 1: Cooling fan running after
power-on
Group F6 PID Function
F6-00
PID
referenc
e source
0˖F6-01
1: AI1
2: AI2
3: PULSE (DI5)
4: MS speed
1 0 ƿ
F6-01
PID
numeric
al value
setup
0.0% to 100.0% 0.1% 50.0% ƿ
F6-02
PID
referenc
e
change
duration
0.0s to 3000.0s 0.1s 0.0s ƿ
F6-03
PID
feedbac
k source
0˖AI1
1˖AI2
2˖PULSE (DI5)
3˖AI1-AI2
1 0 ƿ
F6-04
PID
action
direction
0: Positive
1: Negative
1 0 ƿ
F6-05
PID
referenc
e
feedbac
k range
0 to 65535 1 1000 ƿ
F6-06 Proporti 0.1 to 100.0 0.1 20.0 ƿ