Function Parameter Table MD280/MD280N User Manual
- 98 -
Function code Name Setup Range
Minimu
m Unit
Factory
Default
Value
Change
FA-02
Local
address
0 to 247, 0 is the broadcast
address
1 1 ƿ
FA-03
Respons
e delay
0ms to 20ms 1ms 2ms ƿ
FA-04
Commu
nication
overtime
0.0s to 60.0s 0.1s 0.0s ƿ
FB Fault and Protection
FB-00
Motor
overload
protectio
n
selection
0: Invalid
1:Valid
1 1 ƿ
FB-01
Motor
overload
protectio
n gain
0.20 to 10.00 0.01 1.00 ƿ
FB-02
Motor
overload
prealarm
coefficie
nt
50% to 100% 1% 80% ƿ
FB-03
Over
voltage
stall gain
0 to 100 1 0 ƿ
FB-04
Over
voltage
stall
protectio
n
voltage
120% to 150% 1% 130% ƿ