MD280/MD280N User Manual Function Parameter Table
- 99 -
Function code Name Setup Range
Minimu
m Unit
Factory
Default
Value
Change
FB-05
Over
current
stall gain
0 to 100 1 20 ƿ
FB-06
Over
current
stall
protectio
n current
100% to 200% 1% 150% ƿ
FB-07
Ground
short
circuit
protectio
n upon
power-o
n
0: Invalid
1:Valid
1 1 ƿ
FB-08
Load
fault
protectio
n
function
0: Invalid
1: Valid
1 0 ƿ
FB-09
Transien
t stop/
non-stop
function
selection
0:Invalid
1:Valid
1 0 ƿ
FB-10
Transien
t stop/
non-stop
frequenc
y
reductio
n rate
0.00Hz/s to maximum
frequency(F0-04) /s
0.01Hz/s 10.00Hz/s ƿ