- 336 -
12
Para. No. Para. Name Setting Range Default Property Page
A1-13 VDO3 function selection 34: Zero current
35: IGBT temperature reached
36: Output current exceeding limit
37: Frequency lower limit reached
(having output at stop)
38: Alarm output
39: Motor overheat pending
40: Current running time reached
41: Fault output
0
ƿ
1
8
8
A1-14 VDO4 function selection 0
ƿ
1
8
8
A1-15 VDO5 function selection 0
ƿ
1
8
8
A1-16 VDO1 output delay 0.0s to 3600.0s 0.0s
ƿ
1
8
8
A1-17 VDO2 output delay 0.0s to 3600.0s 0.0s
ƿ
1
8
8
A1-18 VDO3 output delay 0.0s to 3600.0s 0.0s
ƿ
1
8
8
A1-19 VDO4 output delay 0.0s to 3600.0s 0.0s
ƿ
1
8
8
A1-20 VDO5 output delay 0.0s to 3600.0s 0.0s
ƿ
1
8
8
A1-21 VDO active mode selection 00000 to 11111
VDO2:
0: Positive logic active
1: Negative logic active
VDO1:
0: Positive logic active
1: Negative logic active
VDO3:
0: Positive logic active
1: Negative logic active
VDO5:
0: Positive logic active
1: Negative logic active
VDO4:
0: Positive logic active
1: Negative logic active
00000
ƿ
1
8
8
Group A2: Motor 2 Parameters
A2-00 Motor type selection 0 to 1 0
ƾ
1
7
0
A2-01 Rated motor power 0.1 to 1000.0 kW Model
dependent
ƾ
1
7
0
A2-02 Rated motor voltage 1 to 2000 V Model
dependent
ƾ
1
7
0
A2-03 Rated motor current 0.01 to 655.35 A (AC drive power
N:
0.1 to 6553.5 A (AC drive power >
55 kW)
Model
dependent
ƾ
1
7
0
A2-04 Rated motor frequency 0.01 Hz to max. frequency Model
dependent
ƾ
1
7
0
A2-05 Rated motor speed 1 to 65535 rpm Model
dependent
ƾ
1
7
0
A2-06 Stator resistance WRȍ$&GULYH
SRZHUN:
WRȍ$&GULYH
power > 55 kW)
Auto-
tuning
dependent
ƾ
1
7
0