Optidrive P2 Advanced User Guide Revision 2.00
74
www.invertekdrives.com
General Technical and Performance Data
8
8.3. Standby Power Consumption
The following table shows the power consumption of the drive under the following conditions.
Minimum Value measured when the drive is powered from the nominal rated mains supply voltage (e.g. 230 or 400 Volt), output disabled,
cooling fan off, and no external power drawn from the control terminals
Maximum Maximum value with cooling fan operating, 24V, 100mA load on the control terminals
Frame Size
Voltage
Minimum
Maximum
2
230
8
400
10
40
600
3
230
8
400
11
50
600
4
230
11
400
16.7
60
600
5
230
400
19.8
70
600
6
230
400
31.1
96
600
7
230
400
38.5
105
8
400
8.4. DC Bus Discharge Time
DC Bus discharge times are based on maximum rated DC bus, i.e. 480Vac +10% AC supply equates to a DC Bus voltage of 746Vdc within the
drive.
In compliance with EN 61800-5-1:2007, all drives have a caution on the rating labels stating “Power down for 5 minutes before removing
cover”
Frame
Size
Supply
Voltage
DC Bus Voltage
Time to
reach 50V
Max
after 5s
after 60s
2
240Vac +10%
375
324
53
75 sec
480Vac +10%
746
621
64
86 sec
3
240Vac +10%
375
326
40
30 sec
480Vac +10%
746
625
73
120 sec
4
480Vac +10%
746
685
98
182 sec
5
480Vac +10%
746
671
99
179 sec
6
480Vac +10%
746
703
246
181 sec
7
480Vac +10%
746
701
343
190 sec