C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-
0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-
TP.Bắc Ninh
0:
UN
at
lower
limit
FREQ,
Running
at
the
lower
frequency
limit
1:
Run
at
lower
FREQ,
then
sleep,
running
at
the
lower
frequency
limit,
and
sleep
latency.
When
P1.11
is
set
to
be
1,
inverter
will
run
at
lower
frequency
limit.Once
the
delay
time
(P1.12)
is
over,
inverter
will
coast
to
stop;
W
hen
the
setting
frequency
is
higer
than
or
equal
to
the
lower
frequency
limit
again,
inverter
will
be
waked
up
and
autorun
after
delay
time
(P1.13).
Notice:
The
functions
are
invalid
when
P8.00
is
set
to
be
1.
Function
Code
Name
Description
0:
Restart
disabled
Setting
Range
Factory
Setting
P1.14
RESTART
RESTR
DELAY
1:
Restart
enabled
0~1
0
P1.15
TIME
0.0~3600.0s
0.0~3600.0
0.0s
0:
Disabled:
Inverter
will
not
automatically
restart
when
power
on
again
until
run
command
takes
effect.
40
DIEN DAN BIEN TAN HTTP://BIENTAN.HNSV.COM
CHV160A
series
special
inverter
for
water
supply

Table of Contents

Related product manuals