0.0–3600.0s
Time setting on weak-light delay.
When the output frequency is less than or
equal to the PI output frequency lower limit
and the delay counting is started, which
reaches the weak-light delay time, the
system reports the weak-light alarm (A-LS)
and then sleeps. In the non-continuous
situation, the delay counter is automatically
cleared.
Note:
When the bus voltage is lower than
the undervoltage point or the PV
voltage is lower than 70V, the system
directly reports the weak-light alarm
without any delay.
When P15.32=0, in weak-light
condition, the system automatically
switch to the power-frequency input
mode.
0.0–3600.0s
Time setting on weak-light wake-up delay.
If the weak-light pre-alarm is reported, the
system clears the pre-alarm with the
weak-light wake-up delay and then
re-enters the running state.
When P15.32=0, if the PV voltage is
greater than P15.34, the system switches
from the power-frequency input mode to
the PV input mode with the weak-light
wake-up delay.