Goodrive350-19 series VFD Function parameter list
- 203 -
Function
code
Name
Description
Default
value
Modify
When the set frequency is higher than the upper
limit frequency, the VFD runs at the upper limit
frequency.
Setting range: P00.05–P00.03 (Max. output
frequency)
P00.05
Lower limit of
running frequency
The lower limit of running frequency is the lower
limit value of VFD output frequency.
When the set frequency is lower than the lower
limit frequency, the VFD runs at the lower limit
frequency.
Note: Max. output frequency ≥ upper limit
frequency ≥ lower limit frequency.
Setting range: 0.00Hz–P00.04 (upper limit of
running frequency)
0.00Hz
â—Ž
P00.06
Setting channel of
A frequency
command
0: Keypad
1: AI1
2: AI2
3: AI3
4: High speed pulse HDIA
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: MODBUS communication
9: PROFIBUS / CANopen / DeviceNet
communication
10: Ethernet communication
11: High speed pulse HDIB
12: Pulse string AB
13: EtherCat/Profinet communication
14: PLC card
0
â—‹
P00.07
Setting channel of
B frequency
command
1
â—‹

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive350-19 Series and is the answer not in the manual?

INVT Goodrive350-19 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive350-19 Series
CategoryDC Drives
LanguageEnglish

Related product manuals