When the running command channel is controlled
by terminals, the system will detect running
terminal state automatically during power up.
0: Terminal running command is invalid during
power up. The VFD will not run during power up
even if the running command terminal is detected
to be valid, and the system is in running protection
state. The VFD will run only after this terminal is
cancelled and enabled again.
1: Terminal running command is valid during
power up. The system will start the VFD
automatically after initialization is done if the
running command terminal is detected to be valid
during power up.
2: During power on, the terminal-given running
command is invalid, and the POE fault is reported.
During power on, the VFD does not run but reports
the fault, although the running command terminal
is valid. The fault disappears only when the
running command is canceled.
Note: This function must be set with caution,
otherwise, serious consequences may occur.