Goodrive350-19 series VFD Troubleshooting
- 390 -
Grid voltage is too low;
Rated motor current is set
improperly;
Motor stall or load jumps
violently
Check grid voltage;
Reset rated motor current;
Check the load and adjust
torque boost
Acceleration is too fast;
The motor in rotating is
restarted;
Grid voltage is too low;
Load is too large;
Power is too small;
Increase acceleration time;
Avoid restart after stop;
Check grid voltage;
Select the VFD with larger
power;
Select proper motor
Phase loss or violent
fluctuation occurred to R, S
and T input
Check the input power;
Check installation wiring
Phase loss on
output side
Phase loss occurred to U, V,
W output (or the three
phases of motor is
asymmetrical)
Check the output wiring;
Check the motor and cable
Overheat of rectifier
module
Air duct is blocked or fan is
damaged;
Ambient temperature is too
high;
Long-time overload running
Ventilate the air duct or replace
the fan;
Lower the ambient temperature
Overheat of inverter
module
SI external fault input
terminal acts
Check external device input
Baud rate is set improperly;
Communication line fault;
Communication address
error;
Communication suffers from
Set proper baud rate;
Check the wiring of
communication interfaces;
Set proper communication
address;